Phone 866-736-7872
Email sales@microgenius2.com
Menu
Intelligent battery chargers SENS

Standards

 

Conformance to industry and regulatory standards is critical to smooth installation and inspection approvals as well as reliable and safe ongoing system operation.  MicroGenius 2 battery chargers meet or exceed the relevant standards applicable to genset, marine, and standby power applications:

 

Safety

C-UL listed / recognized for the US and Canada to UL 1236 categories BBGQ, BBHH, BBJY and QWIR, CSA 22.2, No. 107.2

CE Mark, Low Voltage Directive, 2014/35/EU (EN 60335-1, EN 60335-2-29)

ABS Type Approved. Meets USCG requirements. 

Ignition Protected per UL 1236, Supplement SB – Marine Battery Chargers

 

Performance

C-UL 1236 performance standards for Emergency & Standby Generators (BBHH) and Engine Driven Fire Pumps (QWIR)

Certified to C-UL supplements SB (marine), SC (firepump), and SE (emergency generator)

NFPA70, NFPA 110

 

Environmental

IBC Seismic – Rigid and non-structure wall mount, max SDS of 2.5G

Water ingress to IP22, NEMA 3R

-40O C to +70O C operating temperature range, convection cooled.  Meets full output specifications to 60O , 50O, and 40O C for models 180, 300, 450 respectively.

Shock & Vibration to EN60068-2-27 (15G), EN60068-2-6 (4G, 18-500Hz)

Electrical Transient to ANSI/IEEE C62.41 & EN 61000-4-2 on power terminals

 

Electromagnetic Conformance

CE Mark, EMC directive, 2014/30/EU (EN 61000-6-2 & EN 61000-6-4)

 

Sustainability

CA Energy Commission Title 20 Appliance Efficiency Regulations

RoHS 2: 2011/65/EU (EN 50581)

European Union WEEE Directive  

Communications

Modbus RS-485

CAN 2.0 extended