EnerGenius IQ
3.01

Release Date: 6/30/2014
Security-Related: No
Summary of Changes: Increased alarm threshold for high AC voltage alarm to avoid possible nuisance alarms. Temperatures now displayed in both degrees C and degrees F.

3.00

Release Date: 7/18/2013
Security-Related: No
Summary of Changes: Added new functionality including Dynamic EqualizeTM charging, commissioning mode, set battery chemistry from control panel, alarm relay/lamp test, and various other feature & reliability improvements.

2.06

Release Date: 1/31/2013
Security-Related: No
Summary of Changes: NiCad strings up to NEMA maximum cell count can now be set per NEMA specifications: 1.600 Volts per cell equalize voltage and 1.750 Volts per cell over-voltage shutdown threshold. Chargers set up for any type of lead-acid battery are not affected by this release.

2.05

Release Date: 4/23/2012
Security-Related: No
Summary of Changes: Improve open DC breaker detection algorithm.
Compatible with Version 2.00 boot loader and SENS SD cards up to 32GB.

2.04

Release Date: 8/11/2010
Security-Related: No
Summary of Changes: Changed behavior of “High Battery Temperature” alarm such that it does not operate the summary relay, does not show the “DC System Alarm” display on line 2 of the default display, does not sound a beep, does not show up in the alarms menu, and does not turn the Battery mimic LED to amber. The IQ will still check for and propagate the alert to the CommsGenius.

——————————————–
EnerGenius IQ Bootloader
2.00

Release Date: 6/14/2012
Security-Related: No
Summary of Changes:

  • Compatible with FAT32 file systems and SENS SD cards up to 32GB.
  • Faster firmware field update operation.
  • Compatible only with IQ functional software version 2.05 or later.
  • NOTE: Bootloader is not field upgradeable. Provided only with new chargers and replacement control boards.
——————————————–
CommsGenius (EnerGenius IQ communications option)
2.01

Release Date: 3/30/2015
Security-Related: No
Summary of Changes: Release 2.01 is a field-installable upgrade for the IQ CommsGenius option that improves communications between the SENS IQ & CommsGenius Setup Utility and the charger.

2.00

Release Date: 9/23/2009
Security-Related: N/A
Summary of Changes: Initial Production Release